simulink系统仿真:10kV 母线短路容量为10MVA,通过额定电压10/0.4kV,额定容量为100kVA,短路阻抗为5%的变压器与负荷相连, 阻感负荷RL 容量为50kVA,功率因数0.9。电力电子装置产生的5 次和7 次谐波电流均为5A;为了抑制7 次谐波在400V 母线处接入电容与变压器构成7 次滤波器。-simulink System Simulation: 10kV busbar short-circuit capacity of 10MVA, through the rated voltage 10/0.4kV, the rated capacity of 100kVA, short-circuit impedance of 5 of the transformer and load connected to sense the load resistance RL capacity 50kVA, power factor of 0.9. Generated by power electronic devices 5 and 7 harmonic currents are 5A to suppress harmonics in the 400V bus 7 access to capacitors and transformers constitute at 7 filter.